Economical Conductivity EC/TDS for Panel or Wall controller to carry out the measurement Conductivity EC in industrial processes, with continuous readings on digital indicators. Suitable for mounting in any industrial panel.
Suitable for small or large industrial water treatment systems, Cooling Towers, Steam Boilers, R.O. etc
Instrument Recognises the buffer solution (EC) and completes the calibration suspending the dosage (HOLD) and showing the electrode’s effciency in %.
Digital Display with high efficency blue leds with 2 lines of 16 digits per line, allows the conteporaneous visualization of 2 parameters: chemical measure and temperature.
Relay output: Set Point 2 (max. resistance load: 10 A 250 VAC). |
This Economical Conductivity EC/TDS for Panel or Wall gives both a valid, low cost measurement and requlation system for large or small industrial and ecological plants, and they can be used as 0/20mA or 4/20mA visualized transmitter for field applications.
Using the programming menu, it is possible to select the available measurement scale to ensure operating versatility with a single instrument.
Technical Data
NX 2000 CD |
|
Measurement Range E. Conductivity
|
C=1.0 , K=1 100÷20.000 μS/cm C=0.2 , K=5 20÷4000 μS/cm C=0.1 , K=10 10÷2000 μS/cm |
Accuracy EC |
1% FS |
Κ Adjustment |
1 , 5 , 10 |
Calibration |
2 Auto/manual for Zero & Sensitive Software assisted |
Temperature Compensation |
Automatic or Manual from 0 to 100 C |
Probe EC Temp |
2 Electrode E.C. probes RTD Pt100 |
Enviroment |
-5 έως 50 C max RM 95% |
Set Point 1 Relay Type Max resistance load Hysterisis Delay Start Delay End |
ON/OFF , Min/Max operation Free Voltage (Dry Contact) 10A 250V AC Yes 3 to 960 Sec 3 to 960 Sec |
Set Point 1 ή Alarm Relay Type Max resistance load Hysterisis Delay Start Delay End |
ON/OFF , Min/Max operation Free Voltage (Dry Contact) 10A 250V AC Yes 3 to 960 Sec 3 to 960 Sec |
Analog Output |
0/4÷20 , 20÷4/0 mA (+/- 2%) |
Password |
Yes 4 Characters |
Statistics |
Yes |
Display | 2 line 16 Character LCD |
Keyboard |
4 Keys |
Power Supply |
90/250 V AC 50/60 Hz |
Marking |
CE |
Instrument Versions
Codes |
Installation
|
Dimensions
|
Protection
|
NX 1000 S |
Wall-mounted (waterproof)
|
144x144x90 mm
|
IP65 (full box)
|
NX 1000 P |
Panel door-mounted
|
96x96x92 mm
|
IP65 (front panel)
|
NX 1000 Q |
Panel door-mounted (half)
|
48x96x100 mm
|
IP40
|
NX 1000 D |
Din Rail panel-mounted
|
|
IP40
|